When should you test an RCD?
Isabella Bartlett
Updated on January 11, 2026
Building and Energy recommends that each RCD be tested every three months. To test your RCD press the 'test' button on the front of the device quickly and then release it. The button will only test the RCD if an electricity supply is connected.
When performing an RCD test the RCD should be tested at?
All RCDs should be tested at least once a quarter, as required by BS 7671, to ensure that they are still operative. This can be carried out by the end user and involves operating the test device (normally a pushbutton) marked 'T' or 'Test'.Why do we test RCDs?
RCD testing is the process of safely "tripping" your RCD to ensure it will operate quickly should there be an electrical incident. This is also known as safety switch testing. Your RCD is designed to trip, or switch off all the power to that circuit.Why tested an RCD at 0 and 180 to ensure?
A Trip test to ensure the RCD trips within the specified time. 4 & 5) both the 1x and 5x tests must be performed at both 0 degrees and 180 degrees (positive and negative supply half cycles) to ensure worst case time is recorded.When should an RCD trip?
In fact, an RCD when tested at its rated sensitivity must trip in 300 ms. When tested at five times, ie, 150 mA for a 30 mA device, it should trip in 40 ms. A 10 mA device must always trip within 40 ms regardless of the test current.Electrical Testing the Tests Required for an RCD Rated at 30mA or Less
What makes a RCD trip?
An RCD can react if there is a sudden rise in electrical current use or leakage current, due to the contents of your refrigerator or freezer thawing out. Occasionally, a poorly connected appliance can cause a spike in electricity supply. If this happens, the RCD will trip and reset as it is designed to do.What circuits need an RCD?
Residual Current Devices (RCDs):In future, all final sub-circuits in residential dwellings must be RCD protected. No exceptions. For non-residential, final sub-circuits up to 32A capacity supplying socket outlets must be 30mA RCD protected. Hard-wired equipment circuits of this capacity should be.